          Walings transfer the forces from the sheet pile wall to the   Owing to the risk of corrosion, structural weld seams must be at least
          anchors and also stiffen and align the wall. Generally, walings   2 mm thicker than as required by the structural calculations.
          are provided in the form of tension members on the inside of
          the main wall, but on anchor walls they are generally provided   The recommendation is to design the walings for the permissible
          in the form of compression members at the rear of the wall.  anchor force of the anchor selected. Besides the horizontal loads
                                                                due to anchor tension, line pull and forces due to imposed loads,
          EAU 2012 recommends providing sturdy walings with generous   walings must also carry vertical loads caused by the vertical anchor
          dimensions, with heavy walings made from S 235 material   component, soil surcharges and self-weight. Horizontal longitudinal
          being preferred over lighter versions made from grade S 355.  forces along the axis of the sheet pile wall, e.g. due to line pull, can
                                                                also occur.